Standards |
|
|
Number of
loops |
1 |
2 |
Addresses
per loop |
200 |
Panel
sounder
circuits |
2 |
Class change
facility |
Operated by
external,
normally
open, volt
free
contacts |
Auxiliary
relay |
One set of
change over
contacts,
operated in
the event of
fire
activation |
Auxiliary
fire routing
equipment
output |
Monitored
24V dc, 30
mA (max) |
Auxiliary
fire
protection
equipment
output |
Monitored
24V dc, 30
mA (max) |
Auxiliary
fault
routing
equipment
output |
Monitored
12V dc, 30
mA (max) |
Output ports |
RS485 and
RS232 (for
connection
of repeaters
etc) |
Mains input
voltage |
230V ac +10%
/ -15% |
System
operating
voltage |
24V dc |
Batteries |
2 x 12V 7Ah |
Extended
battery
option |
|
|
Standby
duration |
24 hours
(subject to
loop load) |
Cable
entries |
11 top entry
cable
knockouts
(20mm) plus
rear entry
cable
aperture |
Environmental
rating |
IP30, -5ºC
to +40ºC,
75% RH (non
condensing) |
Size WxHxD
(mm) |
375x357x50 |
Weight |
8kg |
EB Size
WxHxD (mm) |
|
|
EB Weight |
|
|