General |
Topology |
On-line
double
conversion
with PFC
(Power
Factor
Correction)
system |
Configuration |
Rack/Tower |
Part
Number |
9SX8Ki
|
Rating (VA/Watts) |
8000/7200 |
Dimensions
(H x W x
D, mm) |
440 x
260 x
700 |
Weight
(kg) |
84 |
Warranty |
2 years
warranty |
|
Electrical
Input |
Connection |
Hardwired - see manual for terminal block layout

|
Input
Voltage
Range |
176-276V
without
derating
(up to
100–276V
with
derating) |
Nominal
Voltage |
200/208/220/230/240/250V |
Frequency |
50/60 Hz
autoselection |
Frequency
Range |
40-70 Hz |
Short
Circuit
Current |
120 A |
THDI |
<5% |
|
Electrical
Output |
Voltages |
200/208/220/230/240/250V
+/– 1% |
Voltage
THD |
< 2% |
Output
Receptacles |
Hardwired - see manual for terminal block layout

|
Overload
Capacity |
102–110%
: 120s,
110–125%:
60s,
125–150%:
10s,
>150%:
900ms |
Efficiency
(Normal
Mode) |
Up to
95% in
Online
mode,
98% in
Hi-Efficiency
mode |
Output
Frequency |
50/60 Hz
autoselect,
frequency
converter
as
standard |
Load
Crest
Factor |
3:1 |
|
Battery |
Battery
Management |
ABM® and
Temperature
compensated
charging
method
(user
selectable),
automatic
battery
test,
deep
discharge
protection,
automatic
recognition
of
external
battery
units. |
Extended
Battery
Capability |
EBM |
|
Communications |
User
Interface |
Multilingual
graphical
LCD
display |
Communication
Ports |
1 USB
port, 1
RS232
serial
port
(USB and
RS232
ports
cannot
be used
simultaneously),
4 dry
contacts
(DB9), 1
mini
terminal
block
for
remote
On/Off
and 1
for
remote
power
Off |
Communications
Slot |
1 slot
for
Network-MS
card,
ModBus-MS
or
Relay-MS
cards. |
|
Environmental
&
Standards |
Audible
Noise |
<48dB |
Operating
Temperature |
0 to
40°C
continuous |
Safety
markings |
IEC/EN
62040-1,
UL 1778,
CSA 22.2 |
EMC
Markings |
IEC/EN
62040 -2
, FCC
Class A,
IEC/EN
62040-3
(Performance) |
Approvals |
CE, CB
report (TUV),
UL |