Description |
2 Loop
Control
Panel |
Standards |
EN54 Pt2
1997,
A1:2006
EN$-4 1997,
A1: 2002 &
A2: 2006 |
Specification |
Number of
Loops |
2 |
Addresses
per Loop |
24V dc |
Panel
sounder
circuits |
4 outputs
(programmed
in pairs -
outputs 1&2,
3&4) |
Class change
facility |
Operated by
external,
normally
open, volt
free
contacts |
Auxiliary
relay |
One set of
change over
contacts,
operated in
the event of
fire
activation |
Auxiliary
fire routing
equipment
output |
Monitored
24V dc, 30
mA (max) |
Auxiliary
fire
protection
equipment
output |
Monitored
24V dc, 30
mA (max) |
Auxiliary
Fault
routing
equipment
output |
Monitored
12V dc, 30
mA (max) |
Output ports |
RS485 and
RS232 (for
connection
of repeaters
etc) |
Mains input
voltage |
230V ac +10%
/ -15% |
System
operating
voltage |
24V dc |
Batteries |
2 x 12V 7Ah |
Standby
Duration |
24 hours
(dependant
on loop
loading) |
Environmental |
Operating
Temperature |
-5˚C to 40˚C |
Humidity
(non-condensing) |
0 to 75% RH |
Physical |
Construction |
Back Box –
Mild Steel,
Door –
PC/ABS |
Colour |
Graphite |
Dimensions
WxHxD (mm) |
400x x 320 x
170 |
Weight |
15kg |
Ingress
Protection |
IP30 |
Cable Entry |
Top: 20
entry cable
knockouts
(20mm)
Rear: 7
entry cable
knockouts
(20mm) |